System Set-Up
Hydro Kit
Installation Manual
61
ENGLISH
Summary
• You can set the product user functions.
• Some functions may not be displayed/operated in some product types.
Function text inside
remote
Range
Short explanation
Mid Temp.
High Temp.
Test Run
Cool test run
N/A
Test run operates Multi V in Cooling mode
for max 18 minutes.
3 Minutes delay
N/A
Only for factory testing, cannot change
standby timer compressor restart after
Thermo-Off
Select Temperature
Sensor
Control Standard
- Air temperature(Air)
- Leaving water temp.(Water) (Default)
Sensor Location
- Remote control
- Indoor Unit
Selecting the reference sensor (Air/Water)
for control.
Dry Contact Mode
- Manual
- Auto (default)
Selecting the initial state of the product
when a dry contact signal is input.
Central Control Address
Hexa-decimal address
- 00~FF (default : 00)
When Central Controller is installed,
address assigning is set by this function.
Override Master/Slave
- Master
- Slave (default)
Override master/slave selection function
is to prevent the unit’s different mode
operation. If the unit is set as the slave, it
is blocked to a change of opposite
operating mode(cooling/heating).
Pump test run
Test Run
Checking whether water circulation is
normal.
Air cooling set temp.
- Upper Limitation 24 °C ~ 30 °C
(30 ℃ default)
- Lower Limitation 16 °C ~ 22 °C
(18 ℃ default)
N/A
Adjusting range of 'Setting Air
Temperature' in cooling mode
Water cooling set temp.
FCU is not installed
- Upper limitation 20 ℃ ~ 25 ℃
(24 ℃ default)
- Lower limitation 16 ℃ ~ 20 ℃
(16 ℃ default)
FCU is installed
- Upper limitation 20 ℃ ~ 25 ℃
(24 ℃ default)
- Lower limitation 5 ℃ ~ 20 ℃
(5 ℃ default)
N/A
Adjusting range of 'Setting Leaving Water
Temperature' in cooling mode
Air heating set temp.
- Upper Limitation 24 °C ~ 30 °C
(30 ℃ default)
- Lower Limitation 16 °C ~ 22 °C
(16 ℃ default)
- Upper Limitation 24 °C ~ 30 °C
(30 ℃ default)
- Lower Limitation 16 °C ~ 22 °C
(16 ℃ default)
Adjusting range of 'Setting Air
Temperature' in heating mode
Water heating set temp.
- Upper Limitation 35 °C ~ 50 °C
(50 ℃ default)
- Lower Limitation 20 °C ~ 34 °C
(20 ℃ default)
- Upper Limitation 50 °C ~ 80 °C
(80 ℃ default)
- Lower Limitation 30 °C ~ 46 °C
(46 ℃ default)
Adjusting range of 'Setting Heating Flow
Temperature' in heating mode
DHW set temp.
- Upper limitation 50 °C
(50 ℃ default)
- Lower limitation 30 °C ~ 40 °C
(40 ℃ default)
- Upper limitation 50 °C ~ 80 °C
(80 ℃ default)
- Lower limitation 30 °C ~ 45 °C
(45 ℃ default)
Adjusting range of 'Setting DHW tank
Heating Flow Temperature' in domestic
hot water tank heating mode.