Accessories Installation
Hydro Kit
Installation Manual
39
ENGLISH
Installation Condition
Thermostat
Thermostat is generally used to control the unit by air temperature. When thermostat is connected to
the unit, the unit operation is controlled by the thermostat.
Following location should be avoid to secure proper operation :
• Height from floor is approximately 1.5 m.
• Thermostat can not be located where the area may be hidden when door is open.
• Thermostat can not be located where external thermal influence may be applied. (such as
above heating radiator or open window)
CAUTION
1. Use 230 V AC Thermostat.
2. Some electro-mechanical type thermostat has internal delay time to protect compressor. In that case,
mode change can takes time more than user's expectation. Please read thermostat manual carefully
if the unit does not response quickly.
3. Setting temperature range by thermostat can be different with that of the unit. The heating set
temperature should be chosen within the setting temperature range of the unit.
4. It is highly recommended that the thermostat should be installed where space heating is mainly
applied.
!
1.5 m
Direct
Sun ray contact area
no
no
yes
no
no
no