ADDITIONAL FUNCTIONS
ENGLISH
59
CAUTION
• Ask the licensed installer for the function setup when installing the outdoor unit.
• Set it OFF if you do not use the function.
!
Static pressure compensation mode
Lift the dip switch #5 up to set up the additional functions as you desire by using the buttons.
This function secures the air flow rate of outdoor unit, in case static pressure has been applied
like using duct at fan discharge of the outdoor unit.
Mode Setup
Fan Rotation Setup
Dip switch #5 of the outdoor unit ON
Display "Func" on 7-segment using '
▶
', and
'
◀
' buttons, and press the '
●
' button.
Display "Fu2" on 7-segment using '
▶
', and
'
◀
' buttons, and press the '
●
' button.
Display either "OFF", "op1', or "op2" on
7-segment using '
▶
', and '
◀
' buttons, and
press the '
●
' button.
Operate it at the set RPM
Volume
3Phase 380V 50Hz
1Phase 220V 50Hz
Cooling MAX. fan
RPM
Heating MAX. fan
RPM
Cooling MAX. fan
RPM
Heating MAX. fan
RPM
oFF
950
950
920
920
op1
1000
1000
op2
1020
1000
op3
1050
1000