ELECTRICAL WIRING
ENGLISH
53
Automatic Addressing for Indoor Unit
The address of indoor unit will be set by auto addressing.
- Wait for 3 minutes after supplying power (outdoor unit, indoor unit)
- Press the switch (SW01C) of the indoor unit for 5 seconds.
- “88” will be displayed on the 7-segment LED of the outdoor unit main board.
- It will take 2~7 minutes to complete the auto addressing depending on the number of indoor
units connected.
- After the completion of auto-addressing, the number of the connected indoor units whose
addressing is completed is displayed for 30 seconds on the 7-segment LED of the outdoor
unit main board.
- After the completion of auto-addressing, address of each indoor unit is displayed on the cable
remote control. (CH01, CH02, CH03, …………CH06 : displayed as the number of connected
indoor units)
Main board
7-segment
Dip switch
SW01C
(auto-addressing setup)
• In replacement of the indoor unit PCB, always perform the Auto-addressing settings
again. Make sure to perform the reset with the power of all the outdoor and indoor units
connected. If power supply is not applied to the indoor unit, an operation error will occur.
(Auto-addressing setup cannot be done while the indoor unit is operating.)
• Auto-addressing for has to be performed in 3 minutes after the initial power
supply to improve the transmission.
Turn all the dip switches OFF on the outdoor unit main board before auto-addressing
setup.