OUTDOOR UNIT INSTALLATION
ENGLISH
19
• The nuts #3 and #4 are fixed onto the side of the anti-vibration stand.
• There is an appropriate distance (10 mm) from the bolt #1 and nut #2 to the ODU, as seen in
the picture on the left.
• The bolt should not be touching a concrete floor.
• Non-compliance with the above may cause the outdoor unit to vibrate.
• When using an anti-vibration stand, keep the outdoor unit at least more than 1,500mm from the
first anchor point of the refrigerant pipe.
More than 1,500
Anchor point 1
Unit mm
CAUTION
• Be sure to remove the pallet (wooden support) of the bottom of the outdoor unit bas pan
before using an anchor bolt. It can make the foundation of the outdoor unit unstable, and
may cause freezing of the heat exchanger resulting in abnormal operations.
• Be sure to remove the pallet (wooden support) of the bottom of the outdoor unit before
welding. Not removing the pallet causes hazard of fire during welding.
!
• Install where it can sufficiently support the weight of the outdoor unit. If the support
strength is not enough, the outdoor unit may drop and hurt people.
• Install where the outdoor unit may not fall in strong wind or earthquake. If there is a fault
in the supporting conditions, the outdoor unit may fall and hurt people.
• Please take extra cautions on the supporting strength of the ground, water outlet treat-
ment (treatment of the water flowing out of the outdoor unit in operation), and the pas-
sages of the pipe and wiring, when making the ground support.
WARNING
!
Precautions to take when installing the anti-vibration stand
When installing the anti-vibration stand, inspect the following: