Chapter 9. TROUBLESHOOTING
9 - 2
9.2.1 RUN LED Flickering
G4F – AD2A only
Yes
No
Yes
No
9.2.2 RUN LED Off
Yes
Yes
Yes
9.2 Troubleshooting
RUN LED flickering
RUN LED flickering (per 0.1 sec)?
The channel switch has been set to 0
~
3(Test
mode).
:Set the channel switch to 4
~
F(Normal mode).
RUN LED flickering (per 0.2sec)?
Offset/gain setting has been at incorrect value area.
: Correct Offset/gain setting value.
See the Section 9.2.6
RUN LED off
Correct installation of the A/D conversion
module on the base?
Install the A/D conversion module on the base
correctly.
Capacity sufficient for the power supplies
module on the base?
Calculate current consumption and replace the
power supply module
If the A/D conversion module on which
errors occur is substituted for new one,
normal operation?
The error is occurring on other than the
A/D conversion module.
For more information, see the CPU module
user's manual.
See the Section 9.2.6
No
No
No