2.4.3 G3F-AD4B I/O Characteristics
▶
I/O conversion characteristics are expressed by the angle of used to convert the analog signals(voltage or
current input), input to the PLC into digital values as shown below
▶
A/D coversion module is possible to select voltage/current by analog input range select switch by channel but cannot change
offset/gain value because it is set
I
/O Conversion characteristics
Caution
1. Despite a analog input more than the range of 16000 or 0, digital output value is set to 16000 or 0.
2. Do not apply +15 V /+25 mA or more. This will damage the module due to a heat rise.
Digital
output
16000
12000
8000
4000
0
1V
3V
5V
4
㎃
12
㎃
20
㎃
DC 1 ~ 5V
DC 4 ~ 20
㎃
Analog
input
3.808
㎃
0.952V
20.192
㎃
5.048V