Chapter 8. MK PROGRAMMING
8 - 1
Chapter 8. MK PROGRAMMING
- This shows the method of operation condition setting for buffer memory in the A/D conversion module.
- The A/D conversion module is mounted on the slot 2.
- A/D conversion module occupies 16 I/O points.
8.1.1 G3F-AD4A
8.1 Basic Programming
Slot
No.
Buffer
memory
address
Device
to store
No. of
Words
to write
Execution
condition
Hexa
decimal
decimal
Available channel specification
(channel 0,3,4,12)
Data output type specification
(Used channel is specified by
“0” : -192 ~ 16191)
Filter processing enable/disable
specification
(Filter enable : channel 0,3,4)
Filter constant setting
(Filter constant of channel 0,3 : 10)
Filter constant setting
(Filter constant of channel 4 : 50)
Average processing enable/disable
specification
(Average processing enable of
channel 0,3,12)
Number/time average processing
specification
( Channel 0, 3 : time average
Channel 12 : number average)
Number/time average processing
Constant setting of channel 0 to 3
(Time average processing constant
of channel 0 and 3 : 960 ms)
Number/time average processing
Constant setting of channel 12 to 15
(Number average processing
constant of channel 12 : 100 count)
Set data specification
(channel 0,3,4,12)
A/D conversion value read
(Data read from addresses 14 ~
29 to D0114 ~ D0129)
Channel operation data read
(Channel in operation will be
read)
Error code read
Channel 0 ~ 3 : read to D131
Channel 4 ~ 7 : read to D132
Channel 8 ~ 11 : read to D133
Channel 12 ~ 15 : read to D134
Setting
data.
The
number
of word
to write
Execution
condition