Chapter 7. SPECIAL MODULE COMMAND (BUFFER MEMORY READ/WRITE)
7 - 4
7.2.2 Buffer Memory Write –RPUT
<Format>
RPUT command
execution condition
RPUT SI St S D n SS
<ex>
Slot 4
[configuration]
GM3- K7P- G3I- G3I- G3Q- G3Q- G4L-
PA1A 30AS D24A D22A RY4A RY2A FUEA
Slot 1
GM3- G3L- G3I - G3F-
PA1A RBEA D24A AD4B
[Buffer memory write]
1) Data on D100 to D138(39 words) of the CPU module device
2) is written onto buffer memory address 0 to 38 of A/D conversion module
3) and store information on the statues of communication to D0000.
[program]
[RPUT h0A04 h010B D0100 00000 00039 D0000]
RPUT command
execution condition
AB CD
Symbol
Descriptions
Device used
Sl
Upper(AB): the code vale of A/Conversion module
G3F-AD4A: 00h, G3F-AD4B: 0Ah
G4F-AD2A: 80h
Lower(CD): the slot number of communication module
of the master station.
setting range: 0 to 7
Integer
St
Upper(EF): Slot number of A/D conversion module of
remote station.
setting range: 0 to 31
Lower(GH): communication module number of remote
station.
setting range :0 to 63
Integer
S
First address of device which stores write data.
M, P, K, L, T, C, D, #D
D
First address of special module which will write data.
Integer
n
Number of words of data write.
Integer, D
SS
Condition data display area of link
M, P, K, L, T, C, D, #D
EF GH
To write on buffer memory data of A/D conversion module with RPUT command, configuration the
program so that execution condition of low(0) will be changed into high(1) at rising edge
(
↑
). Or not, buffer memory data of A/D conversion module won't be updated
REMARK
upper lower
(8 bit) (8 bit)
upper lower
(8 bit) (8 bit)
Remote station No.11 (0Bh)