Chapter 2. SPECIFICATIONS
2 - 11
3) Simultaneous Voltage and Current Input Characteristics
For simultaneous voltage and current input, the input conversion switch of each channel is set to corresponding
voltage and current range.
Analog input switch has to be set upward (V1/ I).
Ex) Voltage input range: 0 to 7 Current input range: 8 to 15
Input select switch position
Analog input range switch position
- For simultaneous voltage and current input, voltage input range has to be set only to the range [-5 ~ 5 VDC].
- Simultaneous voltage and current input characteristics lead to digital output value as below.
Analog input
-5.12 V
-5 V
0 V
5 V
5.12 V
Digital output
range
-20.48 mA
-20 mA
0 mA
20 mA
20.48 mA
-192~16191 -192
0
8000 16000 16191
-8192~8191 -8192 -8000
0
8000 8191
Current selection
Voltage selection
V1/ I Voltage:-5~5 VDC
Current:DC-20~20 mA
V2
Digital
Output
Value
8191
8000
0
-8000
-8191
Analog Input