66
_
Inverter Single-60Hz(R410A)
Inverter Single
Inverter Single
7. Capacity tables
AS-W122B1U0
°CWB
°CDB
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
22.0
30.0
24.0
32.0
3.43
3.17
0.49
3.28
3.07
0.51
3.08
2.94
0.68
3.64
3.21
0.66
3.49
3.11
0.66
3.29
3.00
0.80
3.85
3.24
0.71
3.70
3.15
0.72
3.50
3.04
0.84
3.96
3.27
0.72
3.81
3.18
0.73
3.61
3.07
0.85
4.28
3.33
0.72
4.12
3.25
0.74
3.92
3.16
0.87
4.49
3.39
0.72
4.33
3.31
0.75
4.13
3.23
0.89
Outdoor Air Temperature : °CDB
20
25
32
Indoor Air
Temperature
°CWB
°CDB
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
22.0
30.0
24.0
32.0
2.99
2.84
0.76
2.86
2.76
0.84
2.78
2.66
0.82
3.20
2.90
0.86
3.07
2.82
0.90
2.99
2.73
0.86
3.40
2.95
0.88
3.27
2.87
0.91
3.19
2.78
0.86
3.50
2.98
0.88
3.38
2.91
0.92
3.30
2.82
0.85
3.82
3.07
0.92
3.69
3.00
0.93
3.61
2.92
0.86
4.03
3.14
0.94
3.90
3.08
0.95
3.82
2.99
0.88
Outdoor Air Temperature : °CDB
35
40
43
Indoor Air
Temperature
AS-W122BRW0, AS-W122B4A0
°CWB
°CDB
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
22.0
30.0
24.0
32.0
3.43
3.04
0.56
3.28
2.94
0.58
3.08
2.82
0.78
3.64
3.08
0.76
3.49
2.98
0.76
3.29
2.87
0.92
3.85
3.10
0.82
3.70
3.02
0.82
3.50
2.91
0.97
3.96
3.13
0.83
3.81
3.05
0.83
3.61
2.95
0.98
4.28
3.19
0.83
4.12
3.11
0.85
3.92
3.03
1.00
4.49
3.25
0.82
4.33
3.18
0.86
4.13
3.09
1.02
Outdoor Air Temperature : °CDB
20
25
32
Indoor Air
Temperature
°CWB
°CDB
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20.0
16.0
22.0
18.0
25.0
19.0
27.0
22.0
30.0
24.0
32.0
2.99
2.73
0.87
2.86
2.64
0.96
2.78
2.55
0.94
3.20
2.78
0.99
3.07
2.71
1.03
2.99
2.62
0.98
3.40
2.83
1.01
3.27
2.75
1.05
3.19
2.67
0.98
3.50
2.85
1.01
3.38
2.79
1.05
3.30
2.70
0.98
3.82
2.94
1.06
3.69
2.88
1.07
3.61
2.80
0.99
4.03
3.01
1.08
3.90
2.95
1.09
3.82
2.87
1.01
Outdoor Air Temperature : °CDB
35
40
43
Indoor Air
Temperature
Symbol
Notes
AFR : Air Flow Rate
[m
3
/min]
1. All capacities are net, evaporator fan motor heat is deducted.
DB : Dry Bulb Temperature
[°C]
2.
Indicates nominal maximum capacity.
WB : Wet Bulb Temperature
[°C]
3. Direct interpolation is permissible. Do not extrapolate
TC : Total Capacity
[kW]
4. Capacities are based on the following conditions:
SHC : Sensible Heating Capacity
[kW]
- Interconnecting Piping Length 7.5m
PI : Power Input
[kW]
- Level Difference of Zero.
(Comp.+ indoor fan motor + outdoor fan motor)