- 50 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Troubleshooting Guide
Check the TRIAC high speed operation by remote control.
(The Indoor Fan Motor is connected)
Turn off Main power
Check the connection of CN-MOTOR
Check the Fan Motor
Check the Fuse(AC250V/T2A)
Turn ON Main Power
Check the related circuit of indoor Fan Motor.
• The pin NO 58 of Micom, and the part for driving TRIAC(the input and
output signal of IC01M, PIN NO 1, 16)
• Check the pattern
• Check the TRIAC
- TRIAC Open: Indoor Fan Motor never operate
- TRIAC short: Indoor Fan Motor always operates in case of ON or OFF.
When indoor Fan does not operate.
The voltage of PIN NO 1(orange) and 3(yellow) of CN-MOTOR.
About AC 180V over
About AC 50V over
TRIAC is not damaged
TRIAC Check
Summary of Contents for AS-H246DGM0
Page 56: ...P NO 3828A20926G January 2008 ...