Pipe connections between indoor and outdoor unit
Vacuum Mode
This function is used for creating vacuum in the system after compressor replacement, ODU parts replace-
ment or IDU addition/replacement.
Master unit PCB DIP switch on
- Heat pump : switch on 11,14
- Cooling only : switch on 10,12,13
Vacuum mode setting
ODU V/V OPEN
Main EEV, SC EEV OPEN
IDU EEV OPEN
ODU power reset
Press the black button Main PCB (5 sec.)
Vacuum mode setting method
Vacuum mode cancellation method
Master unit PCB DIP switch off
- Heat pump : switch off 11,14
- Cooling only : switch off 10,12,13
Power reset
Vacuum mode cancellation
Installation Manual
51
ENGLISH
CAUTION
ODU operation stops during vacuum mode. Compressor can't operate.