Night Low Noise Function
In cooling mode, this function makes the ODU fan operate at low RPM
to reduce the fan noise of ODU at night which has low cooling load.
Night low noise function setting method
Time Settings
Noise
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn3” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“op1~op12” Push the ‘
●
’ button
Start the Night low noise function :
Save the selected option value in EEPROM
Step
Judgment Time(Hr)
Operation Time(Hr)
op1
8
9
op2
6.5
10.5
op3
5
12
op4
8
9
op5
6.5
10.5
op6
5
12
op7
8
9
op8
6.5
10
op9
5
12
op10
Continuous operation
op11
Continuous operation
op12
Continuous operation
Step
Chassis
UX2
UX3
Noise(dB)
op1~op3, op10
55
59
op4~op6, op11
52
56
op7~op9, op12
49
53
CAUTION
• Request installer to set the function during installation.
• If ODU RPM changes, cooling capacity may go down.
!
Overall defrost mode
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn4” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“on” ~ “oFF” Push the ‘
●
’ button
Overall defrost mode is set
Mode setting
- on: Operate overall defrost
- off: Operate partial defrost
CAUTION
• Ask an authorized technician to setting a function.
• ARUV***BTS4 models do not have Defrost function.
!
Setting the ODU address
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn5” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“0” ~ “255” Push the ‘
●
’ button
ODU address is set
CAUTION
• Ask an authorized technician to setting a function.
• If use a function, first install a Central controller.
!