124
Outdoor Unit
1.2 Night Low Noise Control
ODU Dry contact has provided Two methods for Night Low Noise Control
- Automatically operating
: Using previous method
- Manual operating
: Using simple switch and timer
[Setting]
- For ODU Dry contact
- For Outdoor unit
Refer to DIP S/W setting table
1.3 Error Alarm Monitoring
ODU Dry contact has provided Error Alarm monitoring function
Notice for system fault information by buzzer or warning lamp.
Occurring fault is not only ODUs but also IDUs.
[Setting]
- Note
AC Power : 3A @250V
DC Power : 3A @30V
ON
L1 2
3 4
Connect with S/W or Timer for
Night Low Noise Control
Notes
Default State is L1: ON, L2: ON
Position
Function
ON
L1 2
3 4
ON : Master Mode
OFF : Slave Mode
ON
L1 2
3 4
ON : Enable Low Noise
Operation
OFF : Disable Low Noise
Operation
Error Display
Field Supply
(Depends on Operation
display power type)
Power
AC or DC
New Function