Test Run
96
Outdoor Unit
Display codifica errore controllo sensori
In case error occurs during sensor checking process, error display is as shown below.
Following contents are displayed one after the other on the main PCB of master Unità esterna.
ex) Indoor unit No. 2 Pipe inlet temperature sensor
error
ex) Outdoor Master Unit Liquid pipe temperature
sensor error
ex) IDU No.2 Pipe inlet temperature sensor error and Master
ODU suction temperature sensor, Slave 3 high pressure
sensor error
Caution
1. Up to 5 number of errors is displayed continuously and
repeatedly. In case 5 error occurs, again perform sensor
checking after solving errors.
2. IDU in which error occurred operates air circulation mode.
........
Indoor sensor error :
319
Outdoor sensor error :
309
Displaying error content
* 5 number of errors is displayed
continuously and repeatedly.
No.
Classification
1
Pipe In Temperature
2
Pipe Out Temperature
3
Indoor Air Temperature
Table 2. IDU Sensor Error Code
Table 1. ODU Sensor Error Code
No.
Sensor type
1
2
3
4
5
6
7
8
9
10
11
12
14
15
16
17
Displaying error content
n
Indoor unit error display
1.1st and 2nd number represents indoor unit number.
2. Last number represents sensor.
1: Pipe inlet temperature sensor
2: Pipe outlet temperature sensor
3: Air temperature sensor
n
Displaying outdoor unit error
1. 1st and 2nd number represents error content(code).
2. Last number represents outdoor unit number.
1 : Master
2 : Slave 1
3 : Slave 2
4 : Slave 3
* Indoor unit number follows auto addressing number.
(To check the LGMV Data)
Outdoor Air Temperature
Heat Exchanger Temperature
Partition Heat Exchanger Temperature(Upper)
Partition Heat Exchanger Temperature(Low)
Liquid Pipe Temperature
SC pipe out
Suction Temperature
Inverter Comp. Discharge Temperature
Constant Comp.1 Discharge Temperature
Constant Comp.2 Discharge Temperature
High Pressure
Low Pressure
IPM temperature
INV. Oil Balance Temperature
Constant Comp.1 Oil Balance Temperature 1
Constant Comp.1 Oil Balance Temperature 2
Summary of Contents for ARUB100LT3
Page 132: ...132 Outdoor Unit ...
Page 133: ......