Complete the following checklist for each air cleaner installation.
Table 3: Post-Installation Checklist
Inspection Item
□
Are the air cleaners and return-air plenums-mounted level?
□
Is the fi eld-fabricated ductwork between the air cleaner(s) and the indoor unit sealed and airtight?
□
Are the air cleaners, return-air plenums, and fi eld-fabricated ductwork properly insulated to prevent condensate
from forming?
□
Is the media properly installed? Media pads have a white plastic resin border on one side and either a blue or red
plastic resin border on the other. The side of the pad with the white resin frame always faces upstream and is en-
tering the air side of the pad. Install the media pad(s) with the red edge facing up in the lower clam-shell retainer
of the "V" so when the clamshell frame is closed (raised), the red border will be on the leaving air side. Install
the media pad(s) with the blue edge face down in the upper clamshell of the "V" so when the clamshell frame is
closed (lowered) the blue border will be on the leaving air side.
□
Is the media rotation correct? If the rotation is correct, the metal button on the media pad will align with the mating
receptacle found on the clam-shell expanded metal frame.
□
Are the media pads properly seated in the clamshell frame retainers? Each retainer assembly should close
without using force.
□
Is the air cleaner transformer properly installed and mounted per NEC and local codes?
□
Is the air cleaner low-voltage wire provided with the air cleaner properly connected to the load side of the
transformer?
□
Is the air cleaner low-voltage wire’s quick-connect plug properly seated in the socket on the air cleaner's control
box?
□
Has the indoor unit’s fan speed setting been adjusted to the recommended ESP setting value (see product
engineering manual) to offset additional static pressure consumed by the air cleaner accessory? Refer to the Multi
V Indoor Unit Zone Controller Installation manual for detailed information on how to modify the ESP setting value.
□
Is the return air plenum securely fastened to the air cleaner?
□
Is the return air plenum securely fastened to the return-air grille?
□
Does the return-air grille access door open and close freely without binding or hitting obstructions below?
□
Are all fi eld-fabricated components independently supported so that they do not depend on the indoor unit, air
cleaner, or return air plenum to support their weight?