Dynamic V8
Air Cleaner Installation Manual
Dynamic V8 Air Cleaner
Air Cleaner Installation | 33
Air Cleaner Installation
For continual product development, LG reserves the right to change specifi cations without notice.
LG Electronics U.S.A. Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp./www.lghvac.com
Prepare Air-Cleaner Electrical Connections
1.
Mount the 208/60/1 to 24 VAC low-voltage transformer provided with the air
cleaner in close proximity to the Multi V indoor unit’s
fi
eld-provided disconnect
switch.
Figure 21: Air-cleaner electrical components
2.
Attach
fi
eld-supplied power wire, sized per NEC and local code, from the line
side of the air cleaner transformer to the L1 terminal on the load side of the
fi
eld
provided indoor unit disconnect switch.
3.
Connect the low voltage wire provided with the air cleaner to the 24 V load side
of the transformer as shown in Figure 21.
4.
Connect the male plug provided on the opposite end of the low voltage wire into
the socket on the back of the air cleaner control box. Using tie wraps, securely
attach the low voltage wire between the transformer and the air cleaner to appro-
priate building components to prevent damage and maintain a safe environment.