Multi V Ceiling Cassette Indoor Unit
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CONTROLS SETUP
Slave
Slave
Slave
Master
Slave
Display
Error
Message
▪
Connect Signal and GND lines
between slave indoor units
▪
Do not connect 12V line
between slave indoor units
Display
Error
Message
Master
GND
Signal
12V
AC Smart
ACP Bacnet/ACP LON
(Optional)
Other Building
Mgmt System
(Optional)
LGMV
LGAP Network System
Dry
Contact
(Optional)
Figure 39: Group Control - Method 1
Slave
Slave
Slave
Display
Error
Message
▪
Connect Signal and GND lines between slave indoor units
▪
Do not connect 12V line between slave indoor units
Master
Master
GND
Signal
12V
AC Smart
ACP Bacnet/ACP LON
(Optional)
Other Building
Mgmt System
(Optional)
LGMV
LGAP Network System
Dry
Contact
(Optional)
Figure 40: Group Control - Method 2
Group Control
Figure 39, Figure 40, and Figure 41 show examples of typical control configurations. Figure 39 shows one wired remote controller configured
as a Master to control a group of indoor units. Figure 40 shows two wired remote controllers, one configured as a Master and the other as a
Slave. Figure 41 shows a system with indoor units and fresh air units configured as two groups, each with a Master wired controller. Config-
ure the fresh air units as one group and the standard indoor units as another group. Figure 42 shows both a correct and an incorrect control
configuration for this type of mixed unit system.