REFRIGERANT PIPING
Do not braze in an enclosed location. Do not allow the refrigerant to leak during brazing. Always test
for gas leaks before / after brazing.
3. Flaring the pipe end.
• Use the proper size flaring tool to finish flared connections as
shown.
• ALWAYS create a 45° flare when working with R410A.
Creating a Flare Fitting
One of the main causes of refrigerant leaks is defective flared
connections. Create flared connections using the procedure below.
1. Cut the pipe to length.
• Measure the distance between the indoor unit and the outdoor unit.
• Cut the pipes a little longer than measured distance.
2A. Remove the burrs.
• Completely remove all burrs from pipe ends.
• When removing burrs, point the end of the copper pipe down to
avoid introducing foreign materials in the pipe.
2B. Slide the flare nut onto the copper tube.
90°
Slanted Uneven Rough
Pipe
Reamer
Point
down
Flare nut
Copper
tube
Bar
Copper pipe
Clamp handle
Red arrow
Cone
Bar
Slanted
Smooth
Uneven
Thickness
1.
2A.
2B.
3.
4.
4. Carefully inspect the flared pipe end.
• Compare the geometry with the figure to the right
• If the flare is defective, cut it off and re-do procedure.
• If flare looks good, blow clean the pipe with dry nitrogen.
90°
45°
“A”
R=0.4
– 0.8
Dimensions of the Flare.
Pipe
“A”
≤19,100
1/2
1/4
5/8 – 11/16
7/16 – 1/2
<54,600
5/8
3/8
5/8 – 11/16
5/8 – 11/16
≤76,400
3/4
3/8
3/4 – 13/16
5/8 – 11/16
Flared Connection Dimensions.
Piping Preparation
1. Do not use kinked pipe caused by excessive bending in one specific area on its length.
2. Braze the pipes to the service valve pipe stub of the outdoor unit.
3. After brazing, check for refrigerant gas leaks.
4. When selecting flare fittings, always use a 45° fitting rated for use with high pressure refrigerant R410A. Selected fittings must also
comply with local, state, or federal standards.
Handle
Incorrect Flare
Even Length
Cracked
Yoke
Inside is shiny with no scratches
Surface
Damaged
Copper
tube
If the refrigerant combusts, it generates a toxic gas.