Dedicated Outdoor
Air System (DOAS) Installation and Operation Manual
Network Page
START-UP
Web System Interface
BACnet Local Device Properties
The BACnet local device properties define the JENEsys controller
as a device on the BACnet network. After configuring the proper
network protocol, the local device properties may need to be
configured in order to view the JENEsys controller as the correct
BACnet device. The Object ID is sometimes used by the BACnet
network to uniquely identify devices on the network. In addition, the
Location and Description can also help identify BACnet devices.
1. Enter the Object ID.
2. Enter a Location.
3. Enter a Description.
4. Click the Save button.
Figure 57: BACnet Local Device Properties
Modbus
The Modbus network needs to be enabled and the device address must be set-up. These are the only requirements to initialize the Modbus
network on the JENEsys controller. Other properties may need to be adjusted based on the desired arrangement of the network.
1. Navigate to the network page of the web user interface. There are two tabs of information for the Modbus network.
2. Select true from the Enabled drop-down menu.
3. Expand the ModbusTopSlaveDevice property group.
4. Set the Modbus address to the desired address.
5. Configure any other Modbus config items that need to be changed to match the specific network on the site.
6. Click the Save button.
Figure 58: Modbus Properties