Dedicated Outdoor
Air System (DOAS) Installation and Operation Manual
START-UP
Web System Interface
Home Page
Overriding Values
If a piece of equipment needs to be replaced or tested, the value from the controller
may need to be overridden. Overriding values consist of locking a temperature
sensor to a particular value, or turning a fan or other piece of equipment off/on for a
particular length of time.
Overriding Numeric Values
On the Web Interface Home page, the inputs are displayed as black labels with
white writing and outputs are displayed as gray labels with white text. The colors
can change based on their status. Follow the instructions below to override numeric
values.
1. Right-click the value input. A pop-up window opens.
2. Select Override. The Override Action Menu window opens. The value can be
overridden for a particular duration. The default duration is permanent.
3. Once a value is entered the color changes to pink to indicate that an override is
present and it is not being controlled by the JENEsys controller.
Figure 34: Override Menu
Figure 35: Override Duration
Figure 36: Overridden Value
Overriding Binary Values
On the Web Interface Home page, the inputs have a gray background when they are
false and when its true it is either green, blue or red to indicate its active.
Occasionally a binary input will have a red background when the input is false to
denote a failure (for example, no flow from a water flow sensor). Follow the
instructions below to override a binary signal.
1. Right-click the output value. A pop-up window opens.
2. Select the appropriate action.
• Auto - Clears and overrides actions that are currently in place.
• Active - Overrides the value to true and opens the active menu to set a duration
for the override.
• Inactive - Overrides the value to false and opens the inactive menu to set a
duration for the override.
The default duration is permanent, but any period of time can be entered for the
override duration.
Figure 37: Binary Signal Action
Figure 38: Binary Signal Overridden Value