START-UP
Web System Interface
Network Page
BACnet IP Addressing
BACnet over IP can be set-up on either of the two available ethernet ports.
We recommend using the secondary port for BACnet IP communications and reserving the primary port for connecting to the web user
interface.
The IP addresses for the unit can be changed on the platform page of the web user interface.
1. Navigate to the platform page.
2. Enable the secondary ethernet port.
3. Set the secondary ethernet adapter settings to the desired BACnet IP settings. The BACnet IP network can also be run from the primary
ethernet adapter. Once the ethernet adapter has been set-up correctly the BACnet network and the network page of the web user inter-
face can be used to enable the BACnet IP network and to ensure that the ethernet adapter is selected.
4. Right-click on the Ip Port field, highlight Actions and then select Enable. This will enable the IP port for the BACnet network.
Either the MSTP Port or the IP Port can be enabled on the BACnet network, but they cannot both be enabled at the same time.
Figure 56: IP Port Properties
5. Enter the proper Network Number for the BACnet network in the Network Number field. The network number is determined by the
contractor integrating the unit into the BACnet network.
6. Select the appropriate Ethernet Adapter. The en0 adapter is the primary ethernet adapter and the en1 adapter is the secondary ethernet
adapter. If the desired adapter displays [DISABLED] or [DISCONNECTED], it may need to be enabled. This can be done on the
platform page.
Using the JENEsys Controller as a BBMD
With BACnet over IP, there is an option to use the JENEsys controller as a BBMD for BACnet networks that are split across different IP
subnets.
1. Enter the IP address of a known BBMD in the Bbmd Address field on the IP Port Properties page.
2. Change the Ip Device Type to BBMD.
Once you enter the BBMD address of a known BBMD on a different subnet, the JENEsys controller will connect to that BBMD and populate
the Broadcast Distribution Table with entries from the known BBMD.