INSTALLATION OF THERMOSTAT
25
ENGLISH
To prevent electrical shock and/or equipment damage, disconnect electric power to system
at main fuse or circuit breaker box until installation is complete.
CAUTION
!
NOTE
MERCURY NOTICE:
This product does not contain mercury. However, this product may replace a product that
contains mercury.
Mercury and products containing mercury must not be discarded in household trash.
Refer to www.thermostat-recycle.org for information on disposing of products containing
mercury.
Electrical Rating:
Battery Power ......................................mV to 30 VAC, NEC Class II, 50/60 Hz
Input-Hardwire......................................20 to 30 VAC, NEC Class II, 50/60 Hz
Terminal Load............................................1.5 A per terminal,2.5A maximum
all terminals combined
Setpoint Range..........................................45° to 99° F (7° to 37° C)
Rated Differentials (@ 6°F/ Hr): .................Fast
Med
Slow
Heat (Conventional Gas / Oil / Elect)
0.5°F
0.75°F
1.9°F
Cool (Central Air)
0.9°F
1.2°F
1.7°F
Heat Pump (Heat and Cool)
0.9°F
1.2°F
1.7°F
Heat Pump Aux
0.5°F
0.75°F
1.9°F
Operating Ambient ....................................32°F to +105°F (0° to +41°C)
Display Temperature Range ......................32°F to +99°F (0 to 37°C)
Operating Humidity ...................................90% non-condensing maximum
Shipping Temperature Range ....................-20°F to + 150°F (-29° to +65°C)
Thermostat Dimensions ............................3-3/4” H x 6” W x 1-1/8” D
Specifications