26
INSTALLATION OF THERMOSTAT
ENGLISH
WARNING
!
Refer to equipment manufacturer’s instructions for specific system wiring information.
After wiring, see INSTALLER MENU for proper thermostat configuration.
Wiring table shown are for typical systems and describe the thermostat terminal functions.
Wiring will change when dedicated emergency heat is on (See Installer menu #15).
WIRING
Terminal Designations
Terminal Function
RC
Power (24V) - Cooling
RH
Power (24V) - Heating
O/B
6 (not shown) - 3 wire zone valve
Reversing Valve or output for 3 wire zone valves
Configurable as “O” or “B” Reversing Valve or 3
wire zone heat (power close)
Y
1st Stage Compressor
G
Fan Relay
W/E
1st Stage Heat (conventional);1st Stage Auxiliary
Heat (heat pump) Can operate as Emergency Heat
only (See Installer Menu #15)
C
Common wire for 24V (optional with batteries)
L
Heat Pump Malfunction / Diagnostic terminal (input
signal requires common)
Y2
2nd Stage compressor
W2
2nd Stage Heat (Conventional)2nd Stage Auxiliary
Heat (Heat Pump) Can operate as 1st Stage Auxiliary
Heat (See Installer Menu #15)
Leveling Thermostat
Leveling is for appearance only and
will not affect thermostat operation.
Thermostat Installation