INSTALLATION OF UNIT
ENGLISH
Do not install the unit as indoor unit, install it in an open area, and unit air inlets must not be
located near exhaust vents or other source of contaminated air.
CAUTION
!
Location of unit
When selecting the location for the unit, the following points should be kept in mind:
1. Provisions for a concrete pad or steel stand base.
2. That the terrain allows for drainage away from the unit.
3. If the unit is to be roof mounted, inspect the roof for load bearing capacity. The roof should
have sufficient structural strength to carry the weight of the unit.
4. Install unit on vibration isolation pads, i.e. on rubber mounting pads
5. Availability of electric power.
6. To position the unit for unrestricted air circulation of the condenser air inlet and to prevent any
possibility of air recirculation from the condenser fan discharge air (see figure on next page).
7. Check minimum clearances required for your unit, with regard to walls, or other obstructions
(see figure on next page).
8. Air cooled equipment should not be installed under low structural overhangs which can cause
condenser air recirculation or restriction. Observe minimum of clearance (see figure on next
page).
9. Care should be taken to prevent air from other sources from entering condenser, if this air is at
a high temperature.
10. Level the unit on its final location and be sure that the levelling tolerance is ±5mm per linear
meter in any direction.