Installation of Unit
30
Air-to-Water Heat Pump
3. Installation of Unit
is installed outside to exchange heat with ambient air. Therefore, it is important to
secure proper space around the unit and care for specific external conditions.
This chapter presents a guide to install the unit and what to do when installed around seaside.
General considerations
• If a sunroof is built over the unit to prevent
direct sunlight or rain exposure, make sure that
heat radiation from the heat exchanger is not
restricted.
• Ensure that the spaces indicated by arrows
around front, back and side of the unit.
• Do not place animals and plants in the path of
the warm air.
• Take the weight of the unit into account and
select a place where noise and vibration are
minimum.
• Select a place so that the warm air and noise
from the unit do not disturb neighbors.
• The surface of the ground or the structure must
be strong enough to bear the weight of the unit.
Transport
The unit should be transported to the final
installation site on a wooden pallet. The unit
should be transported by means of a lift truck or
dray.
Installation Conditions
More than
300mm
Fence or
obstacles
More than 700mm
More than 600mm
*Minimum
*Minimum
300mm
300mm
*Minimum
300mm
Sunroof
1. During transport, the unit must not be tilted more than 45°.
2. The unit must not be impacted.
3. The unit more than 30 kg should be transported by two carriers or more.
(Carriers must wear safety protectors.)
4. When the unit is transported by lift truck or dray, be careful not to fall.
5. Be sure to dispose the scraps of vinyl bag, children can be in danger of suffocation.
* : Please secure the space to install the shut-off
valve and strainer.