ENGLISH
CAUTION
• Install declination of the indoor unit is very important for the drain of the duct type air condi-
tioner.
• Minimum thickness of the insulation for the connecting pipe shall be 5mm.
Front of view
• The unit must be declined to the drain hose connected when finished installation.
!
Ceiling
Drainage hole
Drainage hole
CORRECT
INCORRECT
5~10mm
Drainage hole
U-Trap
B
C
A 70 mm
B 2C
C 2 x SP
SP = External Pressure
(mmAq)
Ex) External Pressure
= 10 mmAq
A 70 mm
B 40 mm
C 20 mm
A
Make sure to be closed.
Unit
Drainage pipe
(Local supply)
Thermal insulator
(Local supply)
• Always lay the drain with downward
inclination (1/100 to 1/50).
Prevent any upward flow or reverse flow
in any par t.
• 10 mm or thicker formed thermal insulator
shall always be provided for the drain
pipe.
• Install the P-Trap (or U-Trap) to prevent
a water leakage caused by the blocking
of intake air filter.
Applied U-Trap Dimension
CORRECT
INCORRECT
• Upward routing not
allowed
Caution for gradient of unit and drain piping
Lay the drain hose with a downward inclination so water will drain out.
9
INSTALLATION OF INDOOR