NOTE
1. Be sure to set the value refering table 1. Unexpected set value will cause mal-function.
2. Table 1 is based at 230V. According to the fluctuation of voltage, air flow rate varies.
3. Factory Set(External Static Pressure) each Model
Factory set (E.S.P.)
mmAq(Pa)
Lower Limit (E.S.P)
mmAq(Pa)
Upper Limit (E.S.P)
mmAq(Pa)
6(59)
2.5(25)
14(137)
6(59)
4(39)
12(118)
6(59)
4(39)
12(118)
8(78)
2(20)
10(98)
6(59)
2
.5
(2
5
)
15
(
147
)
2(20)
2(20)
6(59)
15(147)
15(147)
6(59)
Step CMM
Static Pressure[mmAq(Pa)]
2(20) 2.5(25) 3(29) 4(39) 6(59) 8(78) 10(98) 12(118) 13(127) 14(137) 15(147)
Setting Value
HIGH 16.5
85
87
90
94
103
110
118
125
128
131
134
MID
14.5
76
77
85
91
97
107
114
121
125
128
131
LOW
13
73
74
77
88
93
103
111
117
120
125
128
HIGH
18
90
92
95
99
108
115
122
129
132
135
138
MID
16.5
85
87
90
94
103
111
118
125
128
131
134
LOW
14.5
76
77
85
89
97
106
114
121
124
127
130
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
Capacity
-
Phase
18
k - 1Ф
24
k - 1Ф
60k (54k) - 1Ф
60k (54k) - 3Ф
48k - 1Ф
42k - 1Ф
36k - 1Ф
30k - 1Ф
18
k - 1Ф
24
k - 1Ф
Capacity
-
Phase
Step
CMM
Static Pressure[mmAq(Pa)]
2(20) 2.5(25) 3(29)
4(39)
5(49)
6(59)
7(69)
8(78)
9(88)
10(98)
Setting Value
32 : 01 32 : 02 32 : 03 32 : 04 32 : 05 32 : 06 32 : 07 32 : 08 32 : 09 32 : 10
HIGH
22
88
90 92
96
100
104
108
112
116 119
MID
20
80
83 85
90
94
98
103
108
112 115
LOW
18
74
78
76
82
88
94
99
104
108 111
Capacity
-
Phase
30k - 1Ф
(Heating/Cooling)
(Heating/Cooling)
(Heating/Cooling)
28
INSTALLATION INSTRUCTION
ENGLISH