Installation
Service Manual 65
Washer
Nut
Suspension
bolts
Ceiling
Anchor nut
Suspension
bolts
Spring
washer
Max.
12mm
Washer
Nut
1)
2)
Suspension
bolt
Installation plate
Adjust a level
R
Level gauge
Lower slot
R
R
Upper slot
• Insert the nuts and washer into the suspension bolts
for locking the suspension bolts on the ceiling.
• Mount the suspension bolts to the anchor-nuts firmly.
• Secure the Installation plates on Suspension bolts
(adjust level roughly.) using nuts, washers and spring
washers.
• Engage 2 hooks on both left and right side of the unit
to the lower slot of Installation Plates.
• Adjust a level with a level gauge on the direction of
left-right, back-forth by adjusting suspension bolts.
• Move the hooks on the unit to the upper slot of
Installation Plates. Then the unit will be declined to the
bottomside so as to drain well.
Summary of Contents for ABNC186HLAA
Page 79: ...Electronic Control Device Service Manual 79 Ceiling Duct Type ...
Page 80: ...Electronic Control Device 80 Universal System Air Conditioner Ceiling Floor ...
Page 81: ...Schematic Diagram Service Manual 81 Ceiling Cassette Type Schematic Diagram ...
Page 83: ...Schematic Diagram Service Manual 83 Ceiling Duct Type BH BE Series ...
Page 84: ...Schematic Diagram 84 Universal System Air Conditioner Ceiling Floor RY 4WAY RY OUTFAN ...
Page 119: ...P No 3828A22009A Printed in Korea ...