External Static Pressure & Air Flow
Service Manual 59
Table-2
Static Pressure(mmAq.)
Setting Value
0
2
4
6
8
10
Model Name
Step CMM(CFM)
ABNC186HLAA
ABNH186HLAA
ABNC246HLAA
ABNH246HLAA
ABNC306GLAA
ABNH306GLAA
ABNC368GLAA
ABNH368GLAA
16.5(583)
14.5(512)
13.0(459)
18.0(636)
16.5(583)
14.0(494)
26(918)
23(812)
20(706)
32.0(1130)
29.0(1024)
26.5(936)
Hi
Med
Lo
Hi
Med
Lo
Hi
Med
Lo
Hi
Med
Lo
235
245
254
220
235
250
170
185
198
230
240
245
230
238
252
205
230
240
168
183
198
230
240
245
225
235
248
190
220
235
165
181
198
230
240
245
215
230
245
50
200
230
160
180
198
220
235
245
180
215
240
1
100
210
148
177
198
150
230
240
60
165
195
1
220
240
Static Pressure(mmAq.)
Setting Value
0
2
4
6
8
10
CMM(CFM) CMM(CFM) CMM(CFM) CMM(CFM) CMM(CFM) CMM(CFM)
180
22(777)
21(742)
19.8(699)
18.3(646)
16.5(583)
215
18.5(653)
17.8(629)
17.1(604)
16.2(572)
14.5(512)
240
16.1(569)
15.6(551)
15.1(533)
14.2(501)
13(459)
1
24(848)
22.5(795)
20.8(735)
19(671)
18(636)
100
21.3(752)
19.9(703)
18.7(660)
17.2(607)
16.5(583)
210
17(600)
16.1(569)
15.6(551)
14.7(519)
14(494)
60
34.2(1208)
33.1(1169)
31.7(1119)
29.9(1056)
27.7(978
26(918)
165
27(954)
26.3(929)
26.1(922)
25.8(911)
24.8(876)
23(812)
195
21(742)
20.8(735)
20.6(727)
20.4(720)
20.4(720)
20(706)
1
42(1483)
40(1413)
38(1342)
35.5(1254)
33.5(1183)
32(1130)
220
39(1377)
37(1307)
35(1236)
33(1165)
31(1095)
29(1024)
240
34(1201)
32.5(1148)
31(1095)
29.5(1042)
27(954)
26.5(936)
Model Name
Step
ABNC186HLAA
ABNH186HLAA
ABNC246HLAA
ABNH246HLAA
ABNC306GLAA
ABNH306GLAA
ABNC368GLAA
ABNH368GLAA
Hi
Med
Lo
Hi
Med
Lo
Hi
Med
Lo
Hi
Med
Lo
Note: 1. To get the desired Airflow & E.S.P combination from the table set the matching value from
the table. Value other than that in table will not give the combinations of airflow & ESP
which are mentioned in the table.
2. Table 15-2 is based at 230V. According to the fluctuation of voltage, air flow rate varies.
Note: 1) The above table shows the correlation of External Static Pressure & Air Flow.
2) Duct work must go designed within the range of on installing the unit.
3) If duct work is designed under External Static Pressure adjust the External Static
Pressure applying air damper.
Table-3
Summary of Contents for ABNC186HLAA
Page 79: ...Electronic Control Device Service Manual 79 Ceiling Duct Type ...
Page 80: ...Electronic Control Device 80 Universal System Air Conditioner Ceiling Floor ...
Page 81: ...Schematic Diagram Service Manual 81 Ceiling Cassette Type Schematic Diagram ...
Page 83: ...Schematic Diagram Service Manual 83 Ceiling Duct Type BH BE Series ...
Page 84: ...Schematic Diagram 84 Universal System Air Conditioner Ceiling Floor RY 4WAY RY OUTFAN ...
Page 119: ...P No 3828A22009A Printed in Korea ...