EXTERNAL STATIC PRESSURE & FLOW
ENGLISH
23
External Static Pressure(Pa)
60
(Low
EPS)
80
100
120
130
(High
EPS)
140
160
180
200
Model
(Capacity)
Step
30 kBtu/h
Hi (32 CMM)
70
79
86
92
95
98
104
108
110
Med(26 CMM)
67
76
83
89
93
95
102
106
108
Low(20 CMM)
64
74
80
87
91
92
100
104
106
36 kBtu/h
Hi (42 CMM)
77
84
91
96
99
103
107
110
119
Med(36 CMM)
74
80
88
93
96
100
105
108
117
Low(28 CMM)
70
77
84
90
93
96
102
106
115
EXTERNAL STATIC PRESSURE & FLOW
How to set Remote Controller's Switch 2
NOTE
!
Capacities are tested in the following conditions.
Static
Pressure
(Pa)
Voltage
(Phase/Volt)
Air Flow
Step
Piping
Length
Temperaure(°C DB/°C WB)
Cooling
Heating
Indoor
Outdoor
Indoor
Outdoor
60
Ø1/230 V
High
7.5 m
27/19
35/24
20/15
7/6
Remote Controller
For Low E.S.P Mode
For High E.S.P Mode
S/W 2
1
1. Low/Low E.S.P
2. Standard/high E.S.P
3. High/high E.S.P
3
2
How to set RPM
ZONE 1
ZONE 2
ZONE 3
ZONE 4
AUTO INDOOR
REMO
ZONE 1
ZONE 2
ZONE 3
ZONE 4
2TH
REMO
AUTO INDOOR
100 unit
10 unit
1
Press the
button.
2
Press the
button.
4
If you press the
button one more time, the E.S.P
value will be set and the setting mode will be unset.
3
Set the volume of each air flow (Lo
’
Med
’
Hi) by using the
button. Press the
button to select the air flow.
(The value of E.S.P could be adjusted from 1 to 255.)
(Ex. The figure on the left shows when the strong
wind’s ESP value has been set to
127. 127 means 1270 RPM).