Synchronization of multiple HTU330 ultrasonic sensors

If adjacent ultrasonic sensors receive the signals of other sensors, so-called crosstalk occurs, which leads to faulty measurement 

results. Through temporal synchronization of the adjacent sensors, this can be avoided. Via the Sync/MUX input, the HTU330 

ultrasonic sensors can be synchronized in 2 different ways:

Synchronous operation

In this operating mode the mutual interference of adjacent sensors can be avoided; a minimum mounting distance between the 

sensors is to be maintained, however:

Sensors of the same type are wired together in a network according to the following diagram. A synchronization pulse from the 

control activates synchronous operation.
The devices work in synchronous operation with a simultaneous transmission pulse. The response time of the individual sensors 

in the network corresponds approximately to that of a single sensor. 

Synchronous operation wiring schematic

Timing diagram for synchronous operation

Working distance

Minimum mounting distance

< 1,500mm

100mm

u

1500mm

50mm

Sensor 2

Sensor 1

Sensor n

NOTE 

Please make certain that the wiring is performed accord

-

ing to the connection diagram. 

The Sync/MUX pin 5 on all sensors in the network must 

be connected to one output of the control. Generation of 

the synchronization signal for all sensors in the network 

occurs via the control. 

+10 - 30 VDC synchronization pulse 

from the control

PLC

t

sync

t

sync

t

cycle

0 V

+10 - 30 V

Scanning range

Sync impulse duration t

sync

 

Cycle time t

cycle

 

250 … 3500mm

0.5 … 5ms

35ms

350 … 6000mm

0.5 … 1ms

60ms

HTU330

Ultrasonic sensors with 2 switching outputs

Summary of Contents for HTU330 Series

Page 1: ... point can be taught NO NC function reversible 2 independent switching outputs PNP or NPN NEW Both outputs can easily be taught using a button NEW Stable plastic design NEW Temperature compensated scanning range 250 3500mm 350 6000mm Accessories available separately Mounting systems Cables with M12 connector KD Dimensioned drawing A Active sensor surface B Teach in button C Indicator diodes DMU330...

Page 2: ... Plastic PBT Active surface Epoxy resin glass fiber reinforced Weight 140g 170g Ultrasonic transducer Piezoceramic 7 7 The ceramic material of the ultrasonic transducer contains lead zirconium titanate PZT Connection type M12 connector 5 pin Fitting position Any Environmental data Ambient temp operation storage 20 70 C 20 70 C Protective circuit 8 8 1 short circuit and overload protection 2 polari...

Page 3: ...connector pin 4 black cable wire OUT1 4 PNP output NO contact preset P PNP output NC contact preset 2 NPN output NO contact preset N NPN output NC contact preset Pin assignment of connector pin 2 white cable wire Analog OUT OUT2 4 PNP output NO contact preset P PNP output NC contact preset 2 NPN output NO contact preset N NPN output NC contact preset C Analog output 4 20mA V Analog output 0 10V Pi...

Page 4: ...LED OFF Green LED ON Distance Hysteresis Switching point Scanning range OUT not active Yellow blue LED OFF Green LED OFF OUT not active Yellow blue LED OFF Green LED OFF Dead zone Sensor OUT not active Yellow blue LED OFF Green LED ON OUT active Yellow blue LED ON Green LED OFF Distance Hysteresis Switching point Scanning range OUT active Yellow blue LED ON Green LED OFF OUT active Yellow blue LED...

Page 5: ...ior with 2 point window teach as a function of the switching function 1 Place object at desired switching distance 1 First place object at desired switching distance for switching point 1 2 To adjust the selected output press the teach button for 2 7s until the yellow LED OUT 1 or blue LED OUT 2 flashes at 3Hz The current state of the selected output is frozen during the adjustment process 2 To ad...

Page 6: ...d the switching output is changed to the opposite state toggled First activate the previously described teach mode for output OUT 1 or OUT 2 Changeover of the switching function 1 To change the switching function of the selected output press the teach button for longer than 12s The current state of the selected output is frozen during the adjustment process 2 The green and yellow blue LEDs flash a...

Page 7: ...gram A synchronization pulse from the control activates synchronous operation The devices work in synchronous operation with a simultaneous transmission pulse The response time of the individual sensors in the network corresponds approximately to that of a single sensor Synchronous operation wiring schematic Timing diagram for synchronous operation Working distance Minimum mounting distance 1 500m...

Page 8: ...ease the button The green yellow and blue LEDs flash alternately and very quickly for a brief time The sensor was reset to the factory setting switching output OUT 1 NO contact 1 switching point at 3500 mm or 6000 mm static 1 point teach switching output OUT 2 NC contact 1 switching point at 3500 mm or 6000 mm static 1 point teach Sensor 2 Sensor 1 Sensor n NOTE Please make certain that the wiring...

Reviews: