Integrating the LES in the process control
110
Technical description LES
Leuze electronic
When using sensor control command 0x005B with parameter ID 0x07DB, one word of user
data is transmitted to the sensor:
The sensor responds with 0x005C and returns one word of user data.
10.3.4
Commands in measure mode
The following commands are available in measure mode:
Byte
MSB
High-Byte
LSB MSB
Low-Byte
LSB Meaning of the bits
31…32
1
1
1
1
1
0
1
1
0
1
1 Parameter ID for median filter = 0x07DB
Byte
MSB
High-Byte
LSB MSB
Low-Byte
LSB Meaning of the bits
31…32
1 1= median filter active
0= median filter inactive
Command from control to LES
Answer from LES to control
Command no.
Meaning
User
data
words
Command no.
Meaning
User
data
words
0x4554
Ethernet Trigger
With the Ethernet Trigger
command, a single
measurement is triggered
in measure mode, similar to
triggering via the trigger
input..
Prerequisite is that the LES
be configured with LESsoft
under Operation Mode to
Input Triggered.
A connection to the sensor
must exist before the
Ethernet Trigger command
can be used.
0
0x5354
The evaluation telegram is
sent as an answer (status
and measurement values),
see chapter 10.2.9.
1
packet
@ 75
0x414E
The transmitted command
was not processed.
0
Table 10.4:
Commands in measure mode