Display and control panel AMS 335i
48
AMS 335
i
Leuze electronic
8.4
Operation
Described here is an operating process using parameter enabling as an example.
Parameter enabling
During normal operation parameters can only be viewed. If parameters are to be changed,
the
ON
menu item in the
Parameter -> Parameter handling -> Parameter enable
menu must be activated. To do this, proceed as follows:
Viewing and editing parameters
As long as parameter enabling is activated, the entire AMS 335
i
display is inverted.
As long as parameter enabling is activated, communication between control and AMS 335
i
is interrupted. The continued networking via BUS OUT is retained.
In the main menu, press the enter button to enter the
Parameter
menu.
Parameter
Parameter handling
CANopen
Maximum position value
I/O
Other
Use the
buttons to select the
Parameter
handling
menu item.
Press the enter button to enter the
Parameter
handling
menu.
Parameter handling
o Parameter enabling
o
Password
Parameters to default
In the Parameter handling menu, use the
buttons to select the
Parameter enabling
menu item.
Press the enter button to enter the
Parameter
enabling
menu.
Parameter enabling
o
OFF
o ON
In the Parameter enabling menu, use the
buttons to select the
ON
menu item.
Press the enter button to switch on parameter
enabling.
Parameter enabling
o
OFF
ON
The PWR LED illuminates orange; the display is
inverted. You can now set the individual parameters
on the display.
Press the ESC button twice to return to the Param-
eter menu.
ESC
ESC