Electric Power Generation
1
Installation and maintenance
1
5
8
76 en - 2020.01 /
a
TALA44
Low Voltage Alternators - 4 pole
4.8 - Table of characteristics
Table of average values:
Dedicated single-phase M1: 4-pole SHUNT
excitation 4-wire
Alternator - 4 pole - 50 Hz - Winding no. 6S
(6-wire)- no. 6 (12-wire)
The voltage and current values are given for
no- load operation and operation at rated
load with separate field excitation. Ali values
are given at ± 10% (for exact values, consult
the test report) and are subject to change
without priorwarning.
Dedicated single-phase M: 4-pole SHUNT
excitation 4-wire
Resistances at 20 °c (0) - Series
connection
Type
UN stator Rotor Field coil Armature
C
0.024
2.35
11.65
0.423
D1
0.019
2.64
12.94
0.459
J
0.014
3.15
12.94
0.459
Resistances at 20 °C (0) - Series
connection
Type
UL stator Rotor Field coil
C
0.017
2.35
11.65
D1
0.012
2.64
12.94
E
0.013
2.89
12.94
K
0.008
3.43
12.94
LEROY-SOMER '"
Armature
0.423
0.459
0.459
0.459
21