- 12 -
INSTALLATION
4.1 Preparation
4.1.1 Before you install the UPS, give it a through visual examination to ensure it has not been subjected to
shipping damage. If it is not in perfect condition, please contact your local distributor or service center
or e-mail to [email protected].
4.1.2 Installation of the UPS must be done by professional technicians only. Before installing or using this
unit, read all instructions, caution markings on the UPS and all connected load, and all sections of this
user guide.
4.1.3 Check the mains input voltage and alll connected load power rating to suit for UPS power rating.
4.1.4 Transportation
4.1.4.1 UPS has been fitted with casters to allow ease of transportation. UPS must be moved vertically.
4.1.4.2 Transport the UPS with its packaging until it arrive the installation location to avoid shipping
damages.
4.1.4 Location
4.1.5.1 For 2000 VA model or lower: Install the UPS at least 20 cm at the side and back to enable easy
access for installation, operation and maintenance.
4.1.5.2 For 3000 VA model or higher: Install the UPS at least 80 cm free space around the UPS to enable
easy access for installation, operation and maintenance.
4.1.5.3 Install at the floor that is capable of supporting the weight of the UPS.
4.1.5.4 Battery Extension Modules must be installed near by the UPS.
4.1.6 Working with Battery Extension Modules
Batteries are connected in series which have hazardous voltage upto 306-400 Vdc. Any battery
connection must be done by qualified technician only.
Warning:
DO NOT work with batteries when UPS is operating.
4.1.7 Cable size
The cable sizes in the following table are calculated based on TIS. 11-2531 PVC insulated copper wire,
70 degree Celsius conductor temperature, 750 Volt 40 degree Celsius ambient temperature and
maximum 3 wires per conduit.
Note:
-
Maximum cable length must not exceed 10 metres. If in need of cable longer than 10 metres,
properly increase cable size to accommodate excessive length.
-
For your safety, all cables should be wire in the suitable size conduits.
-
The above data is for standard product only.
-
For the battery extension module installation, please contact us.
Power rating
Main input cable (sq.mm.)
Bypass input cable
(sq.mm.)
Output cable (sq.mm.)
PE/Earth cable (
)
(sq.mm.)
1000 VA or lower
Power cord
-
-
-
2000 VA
2.5
2.5
1.5
1.5
3000 VA
2.5
2.5
2.5
2.5
5000 VA
6
6
4
4
6000 VA
6
6
6
4
8000 VA
10
10
6-10
4
10000 VA
16
16
16
6