Commissioning
5-2
820XBA1097
-
In case of condensation connect the controller to mains
voltage only after the visible humidity has evaporated.
-
The plug-in power terminals of the 820X controller must only
be connected or disconnected when no voltage is applied.
Maintain the switch-on sequence!
5.2 Short set-up (Factory setting)
5.2.1
Switch-on sequence
Step
1. Switch on mains voltage
2. Select the direction of rotation.
-
CW rotation:
- Apply a LOW signal to terminal E4 (0...+ 3V).
-
CCW rotation:
- Apply a HIGH signal to terminal E4 (+ 12...+ 30V).
3. Select the setpoint.
Apply a voltage 0...+ 10 V to terminal 8.
4. Enable the controller.
Apply a HIGH signal (+ 12...+ 30V) to terminal 28.
5. The drive is now operating according to factory
setting.