Technical Data
820XBA1097
3-1
3 Technical data
3.1 General data/ application conditions
Field
Values
Vibration resistance
Germanischer Lloyd, general conditions
Humidity class
Humidity class F without condensation (average relative humidity 85 %)
Permissible
temperature ranges
during transport of the controller:
-25
C
¤
+ 70
C
Permissible
temperature ranges
during storage of the controller:
-25
C
¤
+ 55
C
during operation of the controller:
0
C
¤
+ 40
C
+ 40
C
¤
+ 50
C
without power derating
with power derating
Permissible
installation height h
h
$
1000 m.a.m.s.l
1000 m a.m.s.l
h
$
4000 m a.m.s.l
without power derating
with power derating
Degree of pollution
VDE 0110 part 2 pollution degree 2
Noise emission
Requirements acc. to EN 50081-2, EN 50082-1, IEC 22G-WG4 (Cv) 21
Limit value class A to EN 55011 (industrial area) with mains filter
Limit value class B to EN 55022 (residential area) with mains filter and installation into
control cabinet
Noise immunity
Limit values maintained usig mains filter
Requirements according to EN 50082-2, IEC 22G-WG4 (Cv) 21
Requirements
Standard
Severities
ESD
EN61000-4-2
3, i.e. 8 kV with air discharge
6 kV with contact discharge
RF interference(enclosure)
EN61000-4-3
3, i.e. 10 V/m; 27
¤
1000 MHz
Burst
EN61000-4-4
3/4, i.e. 2 kV/5 kHz
Surge
(Surge on mains cable)
EN 61000-4-5
3, i.e. 1.2/50
³
s,
1 kV phase-phase,
2 kV phase-PE
Insulation strength
Overvoltage category III according to VDE 0110
Packaging (DIN
4180)
Dust packaging
Type of protection
IP20
NEMA 1: Protection against contact
Approvals
CE:
Low Voltage Directive
Electromagnetic compatibility
All manuals and user guides at all-guides.com