Installation
820XBA1097
4-11
Terminal
Use
(Factory setting is printed in bold)
Level
Data
Analog
inputs
7
GND 1
inputs
8
Setpoint input,
reference:
Terminal 7
(0 to 10V)
6
4
2
5
3
1
5 - 6
5 - 6
3 - 4
1 - 2
0 to 20 mA
4 to 20 mA
0 to 5 V
0 to 10 V
Resolution: 9 bit
Linearity fault:
0.5 %
Temperature fault: 0.3 % (0...+ 40
C)
Input resistance
Voltage signal: > 100 k
Jumper
Voltage signal: > 100 k
Current signal: 250
9
Supply for setpoint potentiometer
5.2V / 6mA
Analog
output
62
Analog output, reference: terminal 7
(Field frequency)
0... 6 V / 2
mA
Resolution: 8 bit
Digital
inputs
20
Voltage supply for digital inputs
12 V/20 mA
inputs
28
Controller enable
HIGH
HIGH: 12 V ... 30 V
LOW: 0 V ... 3 V
E4
CW rotation/
CCW rotation (CW/ CCW)
CW: LOW
CCW: HIGH
HIGH: 12 V ... 30 V
LOW: 0 V ... 3 V
E3
DC-injection brake
HIGH
E2
JOG frequencies
20Hz, 30Hz, 40Hz
Binary code
E1
JOG frequencies
20Hz, 30Hz, 40Hz
Binary code
39
GND 2 (reference for external voltages)
Terminal
Use
(Factory setting is printed in bold)
Relay position
(switched)
Data
Relay
output
K1
K 11
Relay output normally-closed contact
(TRIP)
opened
24 V AC / 3,0 A or
60 V DC / 0.5 A
output
K1
K 22
Relay mid-position contact
60 V DC / 0.5 A
K 24
Relay output normally-open contact
(TRIP)
closed