36
EDBSV571 EN 1.0
EN
Commissioning
4.5.8.1
Register 2000 - Drive Status Word
Register 2000 - Drive Status Word
Bit
Description
0
1 = Faulted
1
Reserved
2
1 = Running Forward
3
1 = Running Reverse
4
1 = Ready
5
0 = Local Control
1 = Control from Network
6
0 = Local reference
1 = Reference from Network
7
1 = At reference
8
9
10
11
Actual set point source:
0 – keypad
1 – 0-10VDC
2 – 4-20mA
3 – Preset #1
4 – Preset #2
5 – Preset #3
6 – Preset #4
7 – Preset #5
8 – Preset #6
9 – Preset #7
10 – MOP
11 – Network
12
1 = PID Active (closed loop)
13
1 = Torque mode active
14
1 = Current limit
15
1 = DC Braking
4.5.8.2
Register 2002 - Drive Fault
Register 2002 - Drive Fault
Fault #
Description
Fault #
Description
Fault #
Description
0
No Fault
15
Start Fault
30
Internal #11
1
IGBT Temperature Fault
16
Incompatible Parameter Set
31
Internal #12
2
Output Fault
17
EPM Hardware Fault
32
Internal #13
3
Ground Fault
18
Internal #1
33
Internal #14
4
Temperature Fault
19
Internal #2
34
Comm. Module Failure
5
Flying Start Fault
20
Internal #3
35
Network Fault
6
High DC BUS
21
Internal #4
36
Network Fault #1
7
Low DC BUS
23
Internal #6
37
Network Fault #2
8
Overload Fault
24
Internal #7
38
Network Fault #3
9
OEM Fault
25
Internal #8
39
Network Fault #4
10
Illegal Setup Fault
26
Internal #9
40
Network Fault #5
11
Dynamic Brake Fault
27
Internal #10
41
Network Fault #6
12
Phase Lost
28
Remote Keypad Lost
42
Network Fault #7
13
External Fault
29
Assertion Level Fault
43
Network Fault #8
14
Control Fault
44
Network Fault #9