background image

8

EDBSV571 EN 1.0

EN

Technical Data

2.3 Ratings

120V / 240VAC Models

Mains = 120V Single Phase (1/N/PE) (90...132V), 240V Single Phase (2/PE) (170...264V); 48...62Hz

Type

Power

Mains Current

Output Current

Heat Loss (Watts)

Hp

kW

120V

A

240V

A

Cont (In)

A

Max I

%

N1/IP31

ESV371--1S--

0.5

0.37

9.2

4.6

2.4

200

32

ESV751--1S--

1

0.75

16.6

8.3

4.2

200

52

ESV112--1S--

1.5

1.1

20

10.0

6.0

200

74

NOTES:
Output Current: The Output Current Maximum (%) is a percentage of the Output Current Continuous 
Amps (In) rating and is adjustable in parameter P171.

240VAC Models

Mains = 240V Single Phase (2/PE) (170...264V); 48...62Hz

Type

Power

Mains Current

Output Current

Heat Loss (Watts)

Hp

kW

240V

A

Cont (In)

A

Max I

%

N1/IP31

ESV371--2S--

0.5

0.37

5.1

2.4

200

ESV751--2S--

1

0.75

8.8

4.2

200

ESV112--2S--

1.5

1.1

12.0

6.0

200

ESV152--2S--

2

1.5

13.3

7.0

200

ESV222--2S--

3

2.2

17.1

9.6

200

240V Single Phase (2/PE) (170...264V), 240V Three Phase (3/PE) (170...264V); 48...62Hz

Type

Power

Mains Current

Output Current

Heat Loss (Watts)

Hp

kW

1~ (2/PE)

A

3~ (3/PE)

A

Cont (In)

A

Max I

%

N1/IP31

ESV371--2Y--

0.5

0.37

5.1

2.9

2.4

200

27

ESV751--2Y--

1

0.75

8.8

5.0

4.2

200

41

ESV112--2Y--

1.5

1.1

12.0

6.9

6.0

200

64

ESV152--2Y--

2

1.5

13.3

8.1

7.0

200

75

ESV222--2Y--

3

2.2

17.1

10.8

9.6

200

103

Summary of Contents for ESV112N01SXB571

Page 1: ...Frequency inverter SMV Operating instructions EN 13441423...

Page 2: ......

Page 3: ...Display 17 4 2 Drive Display and Modes of Operation 18 4 3 Parameter Setting 19 4 4 Electronic Programming Module EPM 19 4 5 Parameter Menu 20 4 5 1 Basic Setup Parameters 20 4 5 2 I O Setup Parameter...

Page 4: ...Module Installation Instruction CMVMB401 SMVector ModBus RTU over RS485 Communications Reference Guide CMVLC401 SMVector Lecom Communications Reference Guide CMVCAN01 SMVector CANopen Communications R...

Page 5: ...es and regulations take precedence over recommendations provided in this and other Lenze AC Tech documentation The SMVector drive is considered a component for integration into a machine or process It...

Page 6: ...ctive covers and doors prior to and during operation Do not cycle input power to the controller more than once every two minutes For SMVector models that are equipped with a Disconnect Switch 11th cha...

Page 7: ...direct or indirect contact only an RCD or RCM Type B is allowed on the supply side of this product Leakage Current may exceed 3 5mA AC The minimum size of the PE conductor shall comply with local safe...

Page 8: ...ded 100 meters un shielded Enclosure IP31 NEMA 1 IP65 NEMA 4X NEMA 1 and NEMA 4X model enclosures are plenun rated in accordance with UL 508C and are suitable for installation in a compartment handlin...

Page 9: ...751N04TXB571 480 400 VAC 3 phase 1 0 0 75 ESV112N04TXB571 480 400 VAC 3 phase 1 5 1 1 ESV152N04TXB571 480 400 VAC 3 phase 2 0 1 5 ESV222N04TXB571 480 400 VAC 3 phase 3 0 2 2 ESV402N04TXB571 480 400 VA...

Page 10: ...ble in parameter P171 240VAC Models Mains 240V Single Phase 2 PE 170 264V 48 62Hz Type Power Mains Current Output Current Heat Loss Watts Hp kW 240V A Cont In A Max I N1 IP31 ESV371 2S 0 5 0 37 5 1 2...

Page 11: ...Current Heat Loss Watts Hp kW 400V A 480V A Cont In A Max I N1 IP31 400V 480V 400V 480V ESV371 4T 0 5 0 37 1 7 1 5 1 3 1 1 175 200 23 ESV751 4T 1 0 75 2 9 2 5 2 4 2 1 175 200 37 ESV112 4T 1 5 1 1 4 2...

Page 12: ...e Output Current Continuous Amps In rating and is adjustable in parameter P171 STOP For installations above 1000m a m s l derate In by 5 per 1000m do not exceed 4000m a m s l Operation above 40 C dera...

Page 13: ...48 190 7 00 178 0 24 6 4 35 111 0 6 15 2 0 50 2 0 0 9 G2 ESV112 B ESV152 B ESV222 B 3 90 99 3 12 79 7 52 191 7 00 178 0 26 7 5 45 138 0 6 15 2 0 50 2 8 1 3 G3 ESV402 B 3 90 99 3 12 79 7 52 191 7 00 17...

Page 14: ...han 10 times the input kVA rating of the drive s an isolation transformer or 2 3 input line reactor must be added to the line side of the drive s DANGER Hazard of electrical shock Circuit potentials u...

Page 15: ...e motor has an in line contactor or circuit breaker then the drive must be stopped prior to opening closing the contacts Failure to do so may result in 0vercurrent trips and or damage to the inverter...

Page 16: ...e core absorbers on power conductors or alternative practices may be required to meet conformance in some installations Motor cable should be low capacitance core core 75pF m core shield 150pF m Filte...

Page 17: ...M80 A C80 A 80 A 16 6 ESV153N02TXB M100 A C100 A 90 A 16 4 400V or 480V 3 3 PE ESV371N04TXB ESV222N04TXB M10 A C10 A 10 A 10 A 1 5 14 ESV402N04TXB M16 A C16 A 20 A 20 A 2 5 14 ESV552N04TXB M20 A C20...

Page 18: ...als 30 2 11 1 Enable Analog Common Analog Output 4 5 lb in 0 5 Nm AWG 26 16 1mm2 0 25 in 6 mm Control Terminal Strip Descriptions Terminal Description Important 1 Digital Input Start Stop input resist...

Page 19: ...ation direction will blink Press M within 4 seconds to confirm the change The blinking direction LED will turn on and the other LED will turn off When rotation direction is changed while the drive is...

Page 20: ...input is closed the AUTO LED and p q LEDs will both be on 4 2 Drive Display and Modes of Operation Speed Mode Display In the standard mode of operation the drive frequency output is set directly by t...

Page 21: ...s that the drive will be fully operational with the new settings on the next application of power Additionally when the drives parameter settings are burned into an EPM with the EPM Programmer the set...

Page 22: ...etwork 7 Preset Sequence Segment 1 P710 Selections 7 8 9 are not valid for PID setpoint or torque reference 8 Preset Sequence Segment 2 P715 9 Preset Sequence Segment 3 P720 P102 Minimum Frequency 0 0...

Page 23: ...utput rating Example if motor 3amps and SMV 4amps then P108 75 NOTE Do not set above rated motor current as listed on the motor dataplate The motor thermal overload function of the SMV is UL approved...

Page 24: ...TE P110 0 2 Start command must be applied at least 2 seconds after power up F UF fault will occur if start command is applied too soon P110 1 3 6 For automatic start restart the start source must be t...

Page 25: ...to Stop Normally closed Opening input will ramp drive to STOP according to P127 even if P111 is set to Coast 0 or 1 9 Clear Fault Close to reset fault 10 Accel Decel 2 Refer to P125 P126 WARNING Jog...

Page 26: ...9 0 None 2 10 VDC signal can be converted to 4 20 mA with a total circuit impedance of 500 W 1 0 10 VDC Output Frequency 2 2 10 VDC Output Frequency 3 0 10 VDC Load 4 2 10 VDC Load 5 0 10 VDC Torque 6...

Page 27: ...acceleration time increases or the output frequency decreases Digital outputs can also indicate when the limit is reached see P140 P142 Refer to section 2 3 for the maximum output current Max I P172 C...

Page 28: ...bandwidth 0 0 0 0 Hz 10 0 NOTE Bandwidth Hz fs Hz P184 Hz fs P181 or P182 EXAMPLE P181 18 Hz and P184 4 Hz skip range is from 18 to 22 Hz p185 Voltage Midpoint V Hz characteristic 0 0 0 V P165 Valid o...

Page 29: ...only 4 Reset to 50 Hz default settings 5 Translate Refer to Note 5 WARNING Modification of P199 can affect drive functionality STOP and EXTERNAL FAULT circuitry may be disabled Check P100 and P121 P12...

Page 30: ...1 0 PID Display XXXX Applies to P204 P205 P214 P215 P231 P233 P242 P522 P523 1 PID Display XXX X 2 PID Display XX XX 3 PID Display X XXX 4 PID Display XXXX p203 2 PID Units 0 0 Select the UNITS LED t...

Page 31: ...or time longer than P241 or same as Sel 0 P245 Sleep Entry Stop Type 0 0 Coast to Stop 1 Ramp to Stop 2 Stop with P111 settings P246 Feedback Recovery from Sleep Threshold 0 0 P204 P205 Active only wh...

Page 32: ...made to start the drive in Vector or Enhanced V Hz mode before performing the Motor Calibration the drive will display F n1d and will not operate P300 2 3 Same as above but only need to set P302 P304...

Page 33: ...t set to 3 bypass calibration If P300 2 or 3 motor calibration is recommended Use option 2 if option 1 failed or in case of non standard motors An alternating CAL Err will occur if attempt motorcalibr...

Page 34: ...After modification activate with P403 1 8 N 1 2 8 E 1 3 8 O 1 P420 Network Timeout Action 1 0 No action Active when drive is in network control mode Register 2100 bit 5 set Sets the reaction to networ...

Page 35: ...feedback units See P162 P523 TB 25 Feedback P204 P205 TB 25 signal value scaled to PID feedback units See P162 P524 Network Feedback P204 P205 Network signal value scaled to PID feedback units P525 A...

Page 36: ...n the local drive keypad CTRL 4 5 8 Custom Modbus Instructions for ESVxxxNxxxXB571 models Control scheme new register area and control word has been implemented Legacy control scheme utilizing writing...

Page 37: ...put voltage level at terminal Tb30 P150 must be set to 9 Network Control 2103 Digital Relay Output Read Write Reserved Reserved User controlled digital output and relay are not available 2104 Network...

Page 38: ...ription Fault Description Fault Description 0 No Fault 15 Start Fault 30 Internal 11 1 IGBT Temperature Fault 16 Incompatible Parameter Set 31 Internal 12 2 Output Fault 17 EPM Hardware Fault 32 Inter...

Page 39: ...7 Identification in Process 8 Running 9 Acceleration 10 Deceleration 11 Deceleration Override 12 DC Brake 13 Flying start 14 Slow Current Limit 15 Fast Current Limit 16 Sleep mode 4 5 8 4 Register 20...

Page 40: ...r the drive to accept speed from Modbus 7 Reserved 8 9 10 11 Network Speed reference valid when bit 6 set 0 Network 1 keypad 2 0 10VDC 3 4 20mA 4 Preset 1 5 Preset 2 6 Preset 3 7 Preset 4 8 Preset 5 9...

Page 41: ...segments Segment A bit 0 Segment B bit 1 Segment C bit 2 Segment D bit 3 Segment E bit 4 Segment F bit 5 Segment G bit 6 Segment H bit 7 A B C D E F G H Reg 2108 0x7679 HE Reg 2109 0x3873 LP Example...

Page 42: ...Install Dynamic Braking option Err Error Invalid data was entered or an invalid command was attempted FCL Fast Current Limit Overload Verify drive motor are proper size for application fst Flying Res...

Page 43: ...Torque mode C Sequencer mode zz Reference CP Keypad p q EU 0 10 VDC TB 5 E1 4 20 mA TB 25 JG Jog nt Network OP MOP P1 P7 Preset 1 7 01 16 Sequencer Segment Example L S CP Local Keypad Start control Sp...

Page 44: ...d that digital input has been opened P121 3 and that digital input has been closed Correct the external fault condition Make sure digital input is set properly for NC or NO circuit f F1 EPM fault EPM...

Page 45: ...capacitive charging current of the motor cable Use shorter motor cables with lower charging current Use low capacitance motor cables Install reactor between motor and drive Failed output transistor Co...

Page 46: ...Notes...

Page 47: ......

Page 48: ...eet Uxbridge MA 01569 USA 1 800 217 9100 marketing lenzeamericas com www Lenze com Service Lenze AC Tech Corporation 630 Douglas Street Uxbridge MA 01569 USA 1 508 278 9100 1 508 278 6620 repair lenze...

Reviews: