32
EDBSV571 EN 1.0
EN
Commissioning
4.5.6
Network Parameters
Code
Possible Settings
IMPORTANT
No.
Name
Default
Selection
p400
Network Protocol
2
0 Not Active
This parameter setting is based upon the
network or I/O module that is installed.
1 Remote Keypad
2 Modbus RTU
3 CANopen
4 DeviceNet
5 Ethernet
6 Profibus
7 Lecom-B
8 I/O Module
P403
Module Reset
0
0 No Action
Transition 0 -> 1 activates Modbus
related settings in P410, P411, P412 Value
automatically returns to 0
1 Activate Modbus related settings
P405
Current Network
Fault
0
0 No Fault
Network triggered fault by writing into
register 2107
1 F.nF1
2 F.nF2
3 F.nF3
4 F.nF4
5 F.nF5
6 F.nF6
7 F.nF7
8 F.nF8
9 F.nF9
Overall I/O Message Timeout
P410
Network Address
11
1 - 247
Modbus Node address.
After modification, activate with P403
P411
Network Baud Rate
3
0 2400 bps
After modification, activate with P403
1 4800 bps
2 9600 bps
3 19200 bps
4 38400 bps
5 57600 bps
6 125200 bps
P412
Network Data
Format
2
0 8, N, 2
After modification, activate with P403
1 8, N, 1
2 8, E, 1
3 8, O, 1
P420
Network Timeout
Action
1
0 No action
Active when drive is in network control
mode.(Register 2100, bit 5 set)
Sets the reaction to network faults caused
by network timeout or direct writing into
the network fault register 2007.
1 Stop (P111)
2 Quick Stop
3 Controller Inhibit
4 Trip Fault, F.ntF
P421
Network Timeout
15.0
0.0 {sec} 300.0
P430
Display Override
3.0
0.0 {sec} 10.0
P470
Network Messages
Received
0
0
9999
(Read only)
Valid Network messages received.
NOTE:
When the number of messages exceeds 9999, the counter resets and
resumes counting from 0.
P471
Network Messages
Transmitted
0
0
9999
(Read only)
Messages transmitted by the drive.
NOTE:
When the number of messages exceeds 9999, the counter resets and
resumes counting from 0.
P498
Modbus Messages
with Exception
0
0
9999
(Read only)
Modbus messages generating exception
responses.
NOTE:
When the number of messages exceeds 9999, the counter resets and
resumes counting from 0.
P499
Invalid Modbus
Messages
0
0
9999
(Read only)
Invalid Messages received by the drive.
NOTE:
When the number of messages exceeds 9999, the counter resets and
resumes counting from 0.