This chapter lists all EtherNet/IP error messages in the numerical order of the error numbers.
Possible causes and remedies as well as responses to the error messages are described in detail.
EtherNet/IP: Exist. connect. to 8400 lost [0x01bc3100]
EtherNet/IP: Memory: No Access [0x01bc5531]
EtherNet/IP: Memory: Read Error [0x01bc5532]
EtherNet/IP: Memory: Write Error [0x01bc5533] (nt14: COM fault 14)
Response
(Lenze setting printed in bold)
Setting:
C01501/2 (
Adjustable response)
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
Warning
Information
Cause
Remedy
• The Communication Unit is being supplied with
external voltage but the Inverter Drive 8400 motec is
not being supplied with voltage.
• The Communication Unit is not correctly connected
to the Drive Unit.
• Switch the voltage supply of the Inverter Drive 8400
motec off and on again.
• Check wiring and terminals.
• Check internal plug connection between
Communication Unit and Drive Unit.
For this purpose, the Inverter Drives 8400 motec has
to be unscrewed. Please observe the information
provided in the mounting instructions of the
Communication Unit and Drive Unit.
• If this error continues to occur, please contact the
Lenze service. (it might be necessary to replace the
Communication Unit.)
Response
(Lenze setting printed in bold)
Setting:
C01501/2 (
Adjustable response)
No reaction
System fault
Fault
Trouble
Quick stop by trouble
WarningLocked
Warning
Information
Cause
Remedy
Access to memory was not possible.
Send the device and a description of the fault to Lenze.
Response
(Lenze setting printed in bold)
Setting:
C01501/2 (
Adjustable response)
No reaction
System fault
Fault
Trouble
TroubleQuickStop
WarningLocked
Warning
Information
Cause
Remedy
Parameter could not be read.
• Download application again (including module).
• Send the device and a description of the fault to
Lenze.
Response
(Lenze setting printed in bold)
Setting:
C01501/2 (
Adjustable response)
No reaction
System fault
Fault
Trouble
TroubleQuickStop
WarningLocked
Warning
Information
Cause
Remedy
Parameter could not be written.
• Download application again (including module).
• Send the device and a description of the fault to
Lenze.