Electrical installation
Standard devices in the power range 75 ... 90 kW
Mains connection
151
EDK82EV903 DE/EN/FR 5.1
5.5
Standard devices in the power range 75 ... 90 kW
5.5.1
Mains connection
Stop!
ƒ
Only connect the controller to the permitted mains voltage (
Technical
data). A higher mains voltage destroys the controller!
ƒ
Some controllers may only be actuated with a mains choke or mains filter.
This requirement can differ with regard to operation at rated power and
operation at an increased rated power.
ƒ
The leakage current to earth (PE) is > 3.5 mA. In accordance with
EN 61800−5−1 a fixed installation is required. The PE conductor has to be
designed double.
0
L1
L2
L3
N
PE
+UG
-UG
Z1
PE
L1
L2
L3
3/PE AC 400V
T2
T1
L2 L3
L1
3
3
4
L1 L2 L3
+UG
PE
l
3/PE AC 400V
-UG
L1, L2, L3
+UG, -UG
PE
30 Nm
264 lb-in
M10
PE
L1
L2
L3
+UG
PE
l
L1’ L2’ L3’
Gerät / Load
L1 L2 L3 PE
Netz / Line
3/PE AC 400V
Z1
-UG
L1, L2, L3
+UG, -UG
PE
30 Nm
264 lb-in
M10
PE
3
2
T1
T2
2,5 Nm
22.1 lb-in
L1 L2 L3
+UG
PE
l
-UG
L1 L2 L3
3/PE AC 400V
PE
+UG, -UG
PE
M10
30 Nm
264 lb-in
E82EV753K4:
6-12 Nm (53.1-106.2 lb-in)
E82EV903K4:
10-20 Nm (88.5-177 lb-in)
L1, L2,
L3
3
4
1
J>
8200vec290
Connection for mains choke
Connection for footprint mains filter
Connection for built−on mains filter
Connection for braking unit (
Documentation of braking unit)
Temperature monitoring connection for mains filter (thermal contact)
Z1
Mains choke/mains filter