Electrical installation
Standard devices in the power range 15 ... 30 kW
Mains connection
143
EDK82EV903 DE/EN/FR 5.1
5.3
Standard devices in the power range 15 ... 30 kW
5.3.1
Mains connection
Stop!
ƒ
Only connect the controller to the permitted mains voltage (
Technical
data). A higher mains voltage destroys the controller!
ƒ
Some controllers may only be actuated with a mains choke or mains filter.
This requirement can differ with regard to operation at rated power and
operation at an increased rated power.
ƒ
The leakage current to earth (PE) is > 3.5 mA. In accordance with
EN 61800−5−1 a fixed installation is required. The PE conductor has to be
designed double.
PE
L1
L2
L3
+UG
-UG
l
0
L1, L2, L3
+UG, -UG
PE
5 Nm
44 lb-in
M6
3/PE AC 400V
1
L1
L2
L3
N
PE
+UG
-UG
Z1
PE
L1
L2
L3
3/PE AC 400V
T2
T1
L2 L3
L1
PE
2
3
3
3
3
4
4
PE L1’
L2’
L3’
Gerät / Load
Z1
PE
L1
L2
L3
+UG
-UG
l
L1, L2, L3
+UG, -UG
PE
5 Nm
44 lb-in
M6
PE
PE
L1
L2
L3
+UG
-UG
l
+UG, -UG
PE
M6
5 Nm
44 lb-in
3/PE AC 400V
T1
T2
2,5 Nm
22.1 lb-in
L1 L2 L3
L1, L2,
L3
2-5 Nm
17.7-44.3 lb-in
PE
J>
8200vec288
Connection for mains choke
Connection for footprint mains filter
Connection for built−on mains filter
Connection for braking unit
Documentation of braking unit
)
Temperature monitoring connection for mains filter (thermal contact
Z1
Mains choke/mains filter