Table 10. Electrical input connections
Model
Input connection
Input cable
55594-8PX, 5594-8KX
Hardwired
Not provided
5594-9PX, 5594-9KX
Table 11. Electrical output
All models
Normal mode
Battery mode
Voltage regulation
±1%
±1%
Efficiency
> 98% (High Efficiency mode)
> 94.5% for 8-11kVA models
> 91%
Frequency
regulation
Sync with line ±5% of nominal line
frequency (outside this range: ±0.5% of
auto-selected nominal frequency)
±0.5% of auto-selected
nominal frequency
Frequency
50 or 60Hz, autosensing or configurable as a frequency converter
Output overload
100-102% : no alarm
102-110% : load transfers to Bypass mode after 2 minutes
110-125% : load transfers to Bypass mode after 1 minute
125-150% : load transfers to Bypass mode after 10s
> 150% : load transfers to Bypass mode after 900ms
Output overload
(Bypass mode)
100-125% : no alarm
125-150% : UPS shuts down after 1 minute
> 150% : UPS shuts down after 1s
Voltage waveform
Sinewave
Harmonic
distortion
< 2% THDV on linear load
< 5% THDV on non-linear load
Transfer time
Online mode: 0 ms (no break)
High Efficiency mode: 10ms maximum (due to loss of utility power)
Power factor
0.9
Load crest ratio
3 to 1
Table 12. Electrical output connections
Model
Output connection
Output cable
5594-8PX, 5594-8KX
(4) C19 via MBP
Not provided
5594-9PX, 5594-9KX
62
Installation and User's Guide
Summary of Contents for RT11.0VA
Page 2: ......
Page 18: ...xvi Installation and User s Guide ...
Page 22: ...4 Installation and User s Guide ...
Page 86: ...68 Installation and User s Guide ...
Page 98: ...80 Installation and User s Guide ...
Page 100: ...82 Installation and User s Guide ...
Page 101: ......
Page 102: ...Part Number 00WA361 Printed in USA 1P P N 00WA361 ...