Depending on overload conditions, the UPS remains in Bypass mode for at least 5
seconds and will stay in this mode if three transfers to Bypass occur within 20
minutes.
The UPS transfers to Bypass mode when:
v
the user activates Bypass mode through the front panel
v
the UPS detects an internal failure
v
the UPS has an overtemperature condition
v
the UPS has an overload condition listed in the
Specifications
section
Note:
The UPS stops operating after a specified delay for overload conditions
listed in the
Specifications
section. However, the UPS remains on to alarm the fault.
Standby mode
When the UPS is turned off and remains connected to the AC source, the UPS is in
Standby mode (
indicator). Depending if Bypass Standby setting is enabled, the
output is powered but not protected. The battery packs recharge when necessary
and the communication ports are powered.
Operating modes: summary
The following table summarizes the characteristics of your UPS unit in each
operating mode.
Table 3. Operating modes
Mode
Online
Battery
Bypass
Standby
Load
powered
powered
powered
no power
Batteries
charging
discharging
charging
charging
Protection features:
Power failure
yes
n/a
no
no
Power sag
yes
n/a
no
no
Power surge
yes
n/a
no
no
Under voltage
yes
n/a
no
no
Over voltage
yes
n/a
no
no
Line noise
yes
n/a
no
no
Frequency variation
yes
n/a
no
no
Switching transients
yes
n/a
no
no
Harmonic distortion
yes
n/a
no
no
Other features:
Frequency conversion
yes
n/a
no
no
AC source
normal
n/a
bypass
normal
Note:
In High Efficiency mode, the UPS is in Bypass mode and transfers to Battery
mode in less than 10 microseconds (ms) when utility power fails. Transfers to High
Efficiency (HE) mode will be active after 5 minutes of Bypass voltage monitoring:
if Bypass quality is not in tolerance, then the UPS will remain in Online mode.
40
Installation and User's Guide
Summary of Contents for RT11.0VA
Page 2: ......
Page 18: ...xvi Installation and User s Guide ...
Page 22: ...4 Installation and User s Guide ...
Page 86: ...68 Installation and User s Guide ...
Page 98: ...80 Installation and User s Guide ...
Page 100: ...82 Installation and User s Guide ...
Page 101: ......
Page 102: ...Part Number 00WA361 Printed in USA 1P P N 00WA361 ...