Page 15
XP25
ANCHORED HEAVY NYLON
WIRE TIE OR AUTOMOTIVE
MUFFLER‐TYPE HANGER
STRAP LIQUID LINE TO
VAPOR LINE
WALL
STUD
LIQUID LINE
NON-CORROSIVE
METAL SLEEVE
VAPOR LINE - WRAPPED
IN ARMAFLEX
AUTOMOTIVE
MUFFLER‐TYPE HANGER
REFRIGERANT LINE SET — TRANSITION
FROM VERTICAL TO HORIZONTAL
Line Set Isolation
— The following illustrations are examples of proper
refrigerant line set isolation:
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR
WIRE TIE
WIRE TIE (AROUND
VAPOR LINE ONLY)
FLOOR JOIST OR
ROOF RAFTER
TAPE OR
WIRE TIE
TO HANG LINE SET FROM JOIST OR RAFTER, USE EITHER METAL
STRAPPING MATERIAL OR ANCHORED HEAVY NYLON WIRE TIES.
8 FEET (2.43 METERS)
STRAP THE VAPOR LINE TO THE
JOIST OR RAFTER AT 8 FEET (2.43
METERS) INTERVALS THEN STRAP
THE LIQUID LINE TO THE VAPOR LINE.
FLOOR JOIST OR
ROOF RAFTER
REFRIGERANT LINE SET — INSTALLING
HORIZONTAL RUNS
NOTE
- SIMILAR INSTALLATION PRACTICES SHOULD BE USED IF
LINE SET IS TO BE INSTALLED ON EXTERIOR OF OUTSIDE WALL.
PVC
PIPE
FIBERGLASS
INSULATION
CAULK
OUTSIDE
WALL
VAPOR LINE WRAPPED
WITH ARMAFLEX
LIQUID
LINE
OUTSIDE WALL
LIQUID LINE
VAPOR LINE
WOOD BLOCK
BETWEEN
STUDS
STRAP
WOOD BLOCK
STRAP
SLEEVE
WIRE TIE
WIRE TIE
INSIDE WALL
REFRIGERANT LINE SET — INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
INSTALLATION
LINE SET
NOTE - INSULATE LIQUID LINE WHEN IT IS ROUTED THROUGH AREAS
WHERE THE SURROUNDING AMBIENT TEMPERATURE COULD BECOME
HIGHER THAN THE TEMPERATURE OF THE LIQUID LINE OR WHEN
PRESSURE DROP IS EQUAL TO OR GREATER THAN 20 PSIG
.
NON-CORROSIVE
METAL SLEEVE
IMPORTANT -
Refrigerant lines must not contact structure.
NON-CORROSIVE
METAL SLEEVE
8 FEET (2.43 METERS)
IMPORTANT -
Refrigerant lines must not contact
wall
WARNING -
Polyol ester (POE) oils used with
HFC-410A refrigerant absorb moisture very quickly.
It is very important that the refrigerant system be kept
closed as much as possible. DO NOT remove line set
caps or service valve stub caps until you are ready to
make connections.
WIRE TIE
Figure 8. Line Set Installation