Page 37
XP25
Table 7. Outdoor Control 7-Segment Unit Status Displays
Description
Example of Display
Idle Mode
: Decimal point flashes at 1 Hz
Idle Mode: Decimal point flashes at 1 Hz (0.5 second on, 0.5 second off).
Display OFF.
Soft Disabled
: Top and bottom horizontal line and decimal point
flash at 1 Hz.
Soft Disabled: Top and bottom horizontal line and decimal point flash at 1
Hz (0.5 second on, 0.5 second off). Note - Control should be replaced.
Factory Test Mode
All segments flashing at 2 Hz (unless error is detected) Note - Control
should be replaced.
Anti-Short Cycle Delay
The middle line flashes at 1 Hz for 2 seconds, followed by a 2-second dis
play of the number of minutes left on the timer (value is rounded up: 2 min.
1 sec. is displayed as 3). If activated, the anti-short cycle delay time remain
ing is displayed (default is 300 sec./5 min.).
Cooling Cycle
: Shows current percentage of maximum cooling
capacity. Example to the right indicates a cooling demand of 50
percent and a outdoor fan speed of 700 RPM.
The demand percentage is displayed first, followed by a pause, then the
outdoor fan speed and the ambient temperature.
pause
pause
Heating Pump Cycle
: Shows current percentage of maximum
heating capacity. Example to the right indicates a heating de
mand of 33 percent and an outdoor fan speed of 600 RPM.
Following string is repeated if heat pump is active with outdoor fan speed
set at 600 RPM. Note -
- If available, displays outdoor ambient tempera
ture.
pause
pause
Defrost Mode
: Shown only while in an active defrost.
Following string is repeated if defrost is active.
pause
Diagnostic recall:
Shows the last 10 stored diagnostic error
codes.
If first error is
, second
pause
pause
Next codes (up to 10) are show using same method.
Fault memory clears
If there are no error codes stored:
pause
.
After the fault memory
is cleared, the following is displayed with 0.5 seconds character ON / OFF
time:
pause
Active error in outdoor control Idle mode
: Show all active
error(s) codes.
Following display string is repeated if Error E 125 and E 201 are present:
pause
Active error in run mode
: Show current status and all active
error(s) codes.
Following display string is repeated if Error E 440 is present while outdoor
fan speed at 700RPM:
pause
Outdoor Ambient Temperature (OAT)
: Any time OAT is sensed
in operating range, value is displayed if unit is in diagnostic and
non-diagnostic modes.
Following display string is repeated if cooling is active with outdoor fan
speed set at 650 RPM and OAT is 104
º
F:
pause
pause
pause
Outdoor Coil Temperature (OCT)
: Any time OCT is sensed in
operating range, value is displayed if unit is in diagnostic mode
or manually enabled for non-diagnostic modes.
Following display string is repeated if heat is active with outdoor fan speed
set at 550 RPM and OCT is 25
º
F:
pause
pause
pause
Liquid Line Temperature (LIQ
): Any time LIQ is sensed in oper
ating range, value is displayed if unit is in diagnostic mode or
manually enabled for non-diagnostic modes.
Following display string is repeated if cooling is active with outdoor fan
speed set at 650 RPM and LIQ is 105
º
F:
pause
pause
pause
Pump Down Mode
:
While the unit is in pump down mode,
is displayed repeatedly. Errors are shown if they exist.
Following display string is repeated:
pause
pause
pause
pause